AC Size Calculator: BTU, Tons and HP for Your Room

Work out how many BTU/h your room needs and which split unit to buy, in tons, kW and the horsepower (HP) sizes many shops use, from a quick area estimate or a detailed heat-gain calculation for hot climates. Designing the whole system? Browse our MEP Revit families.

Quick or detailed methodBTU/h, tons, kW and HPHot and very hot climate dataHeat-gain breakdown chartRecommended unit size

Method

Quick uses load per floor area. Detailed adds up walls, windows, roof, people and equipment.

Room

m²

Length × width of the room.

Area unit

Homes use the ENERGY STAR sizing chart. Other uses include typical people and fresh air.

Adds 600 BTU/h for each person above two.

A sunlit top-floor roof can add more heat than the rest of the room.

Climate and sun

Summer climate

The hottest outdoor temperature you design for. Moderate: up to 35 °C. Hot: 36–40 °C. Very hot: 41–46 °C.

Sun on the room

Large west-facing windows or single glazing? Use the detailed method for a better figure.

Estimated cooling load

 

Enter your room to see the result.

Estimate only. Quick mode uses rules of thumb; detailed mode is a simplified heat-gain method with typical values, not a full ASHRAE calculation. For design and for equipment schedules, get a full load calculation (for example Carrier HAP, Trane TRACE or the ASHRAE heat balance or RTS method) and check your local code.

Need HVAC Revit families or an MEP model? We build them to your standards.

Request a project
How it works

Size an air conditioner in three steps

1

Choose a method

Use the quick estimate when you only know the floor area, or the detailed method when you know the walls, windows, roof and what is in the room.

2

Describe the room and climate

Enter the area or dimensions, the sun and roof exposure, and pick a climate type or enter your site’s design conditions.

3

Read the load and the unit

You get the load in BTU/h, tons, kW and shop HP size, the smallest standard split size that covers it, and a note when one unit is not enough.

The method

How the cooling load is calculated

Quick estimate. Homes use the ENERGY STAR room air conditioner sizing chart (for example 6,000 BTU/h for 150–250 ft², 12,000 BTU/h for 450–550 ft²) with its adjustments: −10 % for a heavily shaded room, +10 % for a very sunny one, +600 BTU/h for each regular occupant above two and +4,000 BTU/h for a kitchen. Offices, shops, classrooms and restaurants use published square-feet-per-ton rules of thumb. A climate factor of 1.10 (hot, 36–40 °C) or 1.30 (very hot, 41–46 °C) and a top-floor roof allowance are this calculator’s own rules of thumb, taken from its detailed method.

Detailed method. A simplified heat-gain calculation in the style of the ASHRAE CLTD/SCL/CLF method adds up each gain at its peak:

Walls and roof: q = U × A × [(To − DR/2 − Ti) + solar allowance]
Windows: q = A × SCL × SC × shading + U × A × (To − Ti)
People: 75 W sensible + 55 W latent each · Infiltration: q = 1.23·Q·Δt + 3010·Q·ΔW

Lighting and appliances count in full, a 10 % safety factor is added, and 1 W = 3.412 BTU/h. The solar allowances and solar cooling loads are representative values for about 24–32° N in summer, not ASHRAE table values.

Worked example: a 5 × 4 × 3 m room in a hot, dry climate (37.8 °C outdoor) with outside south and west walls in uninsulated brick, 2 m² of south window with blinds and 1.5 m² of unshaded west window, single glazing, 2 people, 100 W lighting and 200 W appliances: walls 817 W, window sun 960 W, window conduction 280 W, people 260 W, lights and appliances 300 W and infiltration 140 W. With 10 % safety that is 3,033 W = 10,348 BTU/h, so a 12,000 BTU/h (1.5 HP) unit. Under a bare concrete roof the same room needs 16,710 BTU/h: an 18,000 BTU/h (2.25 HP) unit.

Estimate only. For design and equipment schedules use a full load calculation such as Carrier HAP, Trane TRACE or the ASHRAE RTS method.

Quick reference

Split unit sizes and design temperatures

Shop label (HP)BTU/hTonskW cooling
19,0000.752.6
1.512,0001.03.5
2.2518,0001.55.3
324,0002.07.0
428,000–30,0002.3–2.58.2–8.8
536,0003.010.6

“HP” (حصان) is the sales label many shops use for split sizes, not the compressor’s power. Ratings vary by brand, so compare the BTU/h on the label. 1 ton of refrigeration = 12,000 BTU/h = 3.517 kW.

ClimateDry bulbWet bulbDaily range
Warm and humid, coastal33 °C22 °C8 K
Hot and dry38 °C21 °C11 K
Very hot and dry44 °C19 °C12 K
Very hot and humid46 °C29 °C10 K

Typical cooling design conditions for each kind of climate, rounded from published 0.4 % design data. For a design, enter your site’s ASHRAE 0.4 % dry bulb and coincident wet bulb, or the values your local code sets.

FAQ

AC size and BTU questions

For a home in a moderate climate, the ENERGY STAR chart gives about 6,000 BTU/h for 150–250 ft² (14–23 m²) and 12,000 BTU/h for 450–550 ft² (42–51 m²). Add about 10 % in a hot climate (36–40 °C) and 30 % in a very hot one (41–46 °C), plus extra for a sunny room, more than two people, a kitchen or a roof above. The detailed mode works it out from the walls, windows and roof instead.

Many shops sell split units by “horsepower”: 1.5 HP is about 12,000 BTU/h, 2.25 HP about 18,000, 3 HP about 24,000 and 5 HP about 36,000. Calculate the load in BTU/h first (حساب قدرة التكييف) and pick the smallest size that covers it. For example, a 5 × 4 m room in a hot, dry climate with south and west windows needs about 10,300 BTU/h, so 1.5 HP; on the top floor under a bare roof it needs about 16,700 BTU/h, so 2.25 HP.

A 1.5 HP split unit is rated at about 12,000 BTU/h, which is 1 ton of refrigeration or 3.5 kW of cooling. The HP figure is a market label, not the compressor’s power: one mechanical horsepower is only 2,545 BTU/h. Always check the BTU/h rating on the unit, as brands differ, especially for 4 HP units (28,000 to 30,000 BTU/h).

Divide BTU/h by 12,000 to get tons of refrigeration, and divide by 3,412 to get kW. So 18,000 BTU/h is 1.5 tons or 5.3 kW, and 24,000 BTU/h is 2 tons or 7.0 kW.

A little margin is fine, and this calculator adds a 10 % safety factor in detailed mode. A unit that is far too large cools the room quickly, switches off before it has removed the moisture and cycles on and off, which feels clammy and wastes energy. Inverter units cope better with oversizing, but sizing close to the load is still best.

Cooling loads use a design temperature that is exceeded only a few hours a year, usually the ASHRAE 0.4 % dry bulb for your site. As a guide, warm coastal climates are around 33 °C, hot and dry ones around 38 °C, very hot and dry ones around 44 °C, and very hot and humid ones around 46 °C with a high wet bulb. Use the value in your local code if it sets one.